24kV Surge Arrester

1 0 0
                                    


The is light in weight, easy and convenient to install on site, and does not need special grounding treatment, and it only needs to meet the natural grounding requirements of the tower.

In case of failure and damage under special circumstances, the overall mechanical and insulation performance of the product will not be damaged, and immediate repair and replacement are not required, but there is no lightning protection function under operating conditions.

Specification of

Rated voltage

17kV

Nominal discharge current

10kA

2ms square wave current

400A

1mA reference voltage

25kV

4/10μs high current impulse

Up to 120kA

Power frequency humidity tolerance voltage

Not less than 13kV